Marginal costs of water savings from cooling system retrofits

A case study for Texas power plants

Bibliographic Data

ID15550461
AuthorsAviva Loew (0000-0001-5717-2741, Carnegie Mellon University, corresponding author), Paulina Jaramillo (0000-0002-4214-1106, Carnegie Mellon University), Haibo Zhai (0000-0001-8585-9559, Carnegie Mellon University)
Year2016
Volume11
Issue10
Pages104004-104004
Publication date2016-10-01
Peer ReviewedYes
Open AccessYes
TypeARTICLE
VenueEnvironmental Research Letters (JOURNAL)
Journal identifiersISSN: 1748-9326 • E-ISSN: 1748-9326
PublisherIOP Publishing (PUBLISHER • GB)
DOI10.1088/1748-9326/11/10/104004
OpenAlexW2528018464
LanguageEN
Citations received2
References cited13

The water demands of power plant cooling systems may strain water supply and make power generation vulnerable to water scarcity. Cooling systems range in their rates of water use, capital investment, and annual costs. Using Texas as a case study, we examined the cost of retrofitting existing coal and natural gas combined-cycle (NGCC) power plants with alternative cooling systems, either wet recirculating towers or air-cooled condensers for dry cooling. We applied a power plant assessment tool to model existing power plants in terms of their key plant attributes and site-specific meteorological conditions and then estimated operation characteristics of retrofitted plants and retrofit costs. We determined the anticipated annual reductions in water withdrawals and the cost-per-gallon of water saved by retrofits in both deterministic and probabilistic forms. The results demonstrate that replacing once-through cooling at coal-fired power plants with wet recirculating towers has the lowest cost per reduced water withdrawals, on average. The average marginal cost of water withdrawal savings for dry-cooling retrofits at coal-fired plants is approximately 0.68 cents per gallon, while the marginal recirculating retrofit cost is 0.008 cents per gallon. For NGCC plants, the average marginal costs of water withdrawal savings for dry-cooling and recirculating towers are 1.78 and 0.037 cents per gallon, respectively

Capital cost · Gallon (US · Power station · Retrofitting · Waste management · Water cooling · Atmospheric and Environmental Gas Dynamics · Engineering · Environmental Science · Water resources management and optimization · Water-Energy-Food Nexus Studies · Environmental Engineering

  • Water usage in cooling systems for electricity production

    Open Access•Kate Hua-Ke, Melissa McCracken•Environmental Research Letters•2024

  • Towards a future-proof climate database for European energy system studies

    Open Access•Laurent Dubus, David Brayshaw et al.•Environmental Research Letters•2022

  • Drought and the water–energy nexus in Texas

    Open Access•Bridget R Scanlon, Ian Duncan et al.•Environmental Research Letters•2013

  • Can switching fuels save water? A life cycle quantification of freshwater consumption for Texas coal- and natural gas-fired electricity

    Open Access•Emily Grubert, Emily A Grubert et al.•Environmental Research Letters•2012

  • Using market-based dispatching with environmental price signals to reduce emissions and water use at power plants in the Texas grid

    Open Access•Nawaf S Alhajeri, Pearl Donohoo et al.•Environmental Research Letters•2011

Unique citing works2
Citations per year0,5
Citation span2022 - 2024 (3)
Citation velocityrecent
Highly citedNo